Table 3

Particle emission after rubbing white cardboard boxes expressed as mean particles ≥0.5 and ≥5 µm per m3

Cardboard boxes fromParticles ≥0.5 µm/m3
(n=5)
Particles ≥5 µm/m3
(n=5)
MeanSDMeanSD
Soluvit N*81 95969 02280497181
Vitintra adult*22 260740435131561
Ampoules 10 mL75 14637 86316 06413 237
Supleven34 08610 6353460688
Overall mean†53 36219 94677713788
Limits airborne particle for Grade C in operation3 520 00029 000
P-value for overall mean; limit is reference group<0.001<0.001
  • *Laminated cardboard.

  • †Overall mean of all 20 determinations.

  • n, number of samples examined.